Horse Power | Electrical Requirements | SKU | Price |
---|---|---|---|
HH-15 (1/2hp) | 230V | JT:AAH67011K |
$10,711
|
HH-20 (3/4hp) | 230V | JT:AAH67021K |
$12,196
|
HH-25 (1hp) | 230V | JT:AAH67031K |
$14,374
|
HH-35 (1.5hp) | 230V | JT:AAH67041K |
$15,661
|
HH-45 (2hp) | 380V | JT:AAH67159K |
$19,324
|
HH-55 (3hp) | 380V | JT:AAH67169K |
$20,808
|
Broad temperature ranging up to 80°C for various applications.
Also integrated heaters greatly provide high temperature stability.
Models: HH-15/20/25/35/45H/55H
Performance
Convenience
Safety
Please note: Jeio Tech recirculating coolers are generally not stocked in the US, are built-to-order in Korea, and are shipped via ocean freight. An 8-12 week lead time should be expected.
Type | Chillers |
Incubation | Yes |
Refrigeration | Yes |
Temp Range (°C) | -20 to 80 |
Capacity (L) | 13.5, 25, 39 |
Circulation | External Only |
Brand | Jeio Tech |
MaxFlow Rate (l/min) | 40, or 70 |
Temp Stability (°C) | ±1°C |
Timer | No |
Alarms | Yes |
Digital or Mechanical | Digital |
Data connection | Yes |
Tank Material | N/A |
Sample Agitation | No |
Media Racks Available | No |
Warranty (years) | 1 (2 years after submission of warranty registration card) |
Weight (lb) | 203-388 |
Model | HH-15 | HH-20 | HH-25 | HH-35 | HH-45H 2) | HH-55H 2) | |
---|---|---|---|---|---|---|---|
Temperature 1) (bath fluid : ethylene glycol mix 1:1 water) | Working temperature range (℃ / ℉) | -20 to 80 / - 4 to 176 | |||||
Temperature stabilityat 15℃ (±℃ / ℉) | 0.1 / 0.2 | ||||||
Cooling capacity(bath Fluid : ethylene glycol mix 1:1 water) | at 80℃ (kw) | 2 | 2.5 | 3.5 | 4 | 6 | 7.5 |
at 40℃ (kw) | 0.9 | 1 | 2.4 | 2.5 | 4.5 | 5 | |
at 20℃ (kw) | 1.45 | 1.8 | 2.5 | 3.3 | 6.5 | 7.1 | |
at 0℃ (kw) | 0.86 | 1.15 | 1.1 | 1.7 | 3 | 4.1 | |
at -20℃ (kw) | 0.3 | 0.4 | 0.4 | 0.55 | 1.2 | 1.5 | |
Heating capacity(kw) | 2 | 4 | 8.4 | ||||
Pump | Max. flow rate(L / min, gal / min) | 40 / 10.6 | 70 / 18.5 | ||||
Max. pressure (bar / psi) | 3.3 / 47.9 | 6 / 87.02 | |||||
Dimension | Max. filling capacity (L, cu ft) | 13.5 / 0.47 | 25 / 0.88 | 39 / 1.37 | |||
For tubing dia. (mm / inch) | 20 / 3/4 | ||||||
Filling inlet (Ø, mm / inch) | 120 / 4.7 | ||||||
Overall (WxDxH, mm / inch) | 515×715× 835/ 20.3×28.1×32.9 | 550×900×1140/ 21.7×35.4×44.9 | 605×1045×1300/ 23.8×41.4×51.2 | ||||
Net weight (kg / Ibs) | 92 / 202.8 | 93 / 205 | 142 / 313 | 147 / 324 | 171±10/ 377±22 | 176±10/ 388±22 | |
Electric requirement (230V, 60Hz) | 15A | 16A | 27A | 31A | - | - | |
Electric requirement (380V, 60Hz) | - | - | - | - | 18.3 | 19.8 |
1) Technical data according to DIN 12876.
2) HS-45H, 55H is recorded by 380V, 60Hz.
※ Above specification value is recorded by 50Hz.
※ Product performance may be affected by ambient temperatures.
※ Under the condition of no-load operation, cooling capacity should be lower than heating capacity.